Flowline LI55-1001 DataView Level Controller, Meter Only, No Repeater, 85-265 VAC
The general purpose level controller displays engineering units with one 4-20 mA or 0-10 VDC continuous level sensor input and is offered in three configurations with optional 2 or 4 programmable relays, and an isolated 4-20 mA repeater. Each relay can be configured on a single set point (high level alarm or low level alarm) or latched on two set points for automatic fill or empty in simplex (one pump or valve) or duplex (two pumps) level control modes. For field mount installation in a NEMA 4X, corrosion resistant polycarbonate enclosure, order the appropriate single or two indicator box. Each enclosure comes with precut panels and mounting hardware. It€s indication and control made simple. Display type: LED, 6-digit. Display units: Engineering. Display output: -99999 to 999999. Display height: Main: 0.6" (15mm) high. Secondary: 0.46" (12mm). Decimal point: Floating. LED indication: Relay status. Configuration: Push button. Memory: Non-volatile. Linearization: 2-32 point function. Sensor input: (1) 4-20 mA or 0-10 VDC. Supply voltage: 85-265 VAC at 50-60 Hz. Consumption: 15 watts maximum. Sensor supply: 24 VDC +/- 5 degree at 200 mA. Repeater output: 4-20 mA, 24 VDC +/- 5 percent at 40 mA supply. Contact type: -12_1: (2) SPDT relays-14_1: (4) SPDT relays. Contact rating: 3A at 30 VDC and 250 VAC resistive load. Ambient temperature: F: -40 to 149 degree, C: -40 to 65 degree. Enclosure type: 1/8 DIN, panel mount. Enclosure rating: NEMA 4X (IP65) faceplate. Enclosure material: Polycarbonate. Classification: General purpose. Compliance: CE. Approvals: UL, cUL listed, E160849, 508 industrial control equipment.